Panda Group of Companies

Ammonia refrigerating plant for distribution centre in Riyadh

Key information

Client:

Panda Group of Companies

Supplier:

Johnson Controls International

Type of facility:

Central ammonia refrigerating plant

System start-up:

2008

The Saudi Arabian food retailer Panda Group of Companies built a state-of-the-art distribution centre in Riyadh that was put into operation in 2008. For this purpose Johnson Controls International implemented a central ammonia refrigerating plant.


Requirements

The food retailer was interested in a central refrigeration design that had to be energy- and cost-efficient.


Solution

The refrigeration needed for the different store rooms is generated centrally by three systems:

a) HT gravity circulation ammonia system using two T20-BWFG plate heat exchangers with three Frick screw compressors RXF68, 1,018 kW each, two on-duty and one stand-by producing 12 ºC; one chilled water facility for cooling the regular storage rooms

b) MT gravity circulation ammonia system using two T20-MWFG plate heat exchangers with 4 Frick screw compressors RWF II-134, 750 kW each, all on-duty producing chilled propylene Glycol at -10 ºC required for all MT applications

c) LT pump circulation system with two -36 ºC low-stage compressors RWF II-134 , 330 kW each, all on-duty with one swing compressor RWF II-134, 750/330 kW, for LT freezer room applications

7 banana ripening rooms connected with the MT glycol circuit, controlled by 110 propa controllers via central PC

2 forced-air wet coolers with -12 ºC pump circulation system connected with the MT system; serves to pre-cool all vegetables

All systems are controlled and monitored by a central PC unit using Johnson Controls DDC controllers FXO6, FX14, FX16. All coolers were assembled with variable-speed, built-in fan motors. I.e. the speed and temperature can be controlled to reduce power consumption and running costs.

Technical data

Cooling capacity:

HT = 2,036 kW at 12 ºC, MT = 3,000 kW at -13 ºC, LT = 660 kW at -36 ºC

Refrigerant volume:

500,000 m³ in the HT areas at 12 ºC, 60,000 m³ in the MT areas at different medium temperatures, 22,000 m ³ in the LT freezer rooms

Secondary refrigerant:

Water, glycol

Main components:

  • Screw compressors by Frick

  • Module-welded plate heat exchangers by Alfa Laval

  • Evaporative condenser by BAC

  • Evaporators and air coolers by Thermofin

Special features:

Glycol absorbs the heat given off by the ammonia going through the plate heat exchangers. The hot glycol circuit is then used for MT defrosting and under-floor heating.